How to initiate auto-calibration | DIGIWAY Door Automation

How do I initiate auto-calibration?

Before starting the auto-calibration, you need to set the spring pre-load tension and set the door limits
For instructions for the full calibration process, view this article.
When you are ready to initiate the auto-calibration, open the DIGIWAY app and find the right unit that you want to calibrate. 
  1. Hold down OK to enter the programming menu. 
  2. From the menu, select Door Calibration
  3. Change the door to Free Mode using the slider in the bottom-left corner of the app screen. 
  4. From the menu, select Auto-Calibration.
  5. Then, press OK again to confirm and proceed to auto-calibration.
  6. The door will open and close five times to calibrate itself. 
  7. Once the calibration is complete, exit the menu and switch the door back to Auto Mode using the slider.
After you have calibrated the DIGIWAY, test the opening and closing mechanism by pressing the Open/Close icon on the app.



    • Related Articles

    • DIGIWAY Plus auto-calibration troubleshooting

      General advice for setting up Fit the unit and arm as per the diagrams in the installation manual. The door must be completely free swinging with a physically defined close point - i.e. not a swing-through door. To begin with, keep the setup as basic ...
    • DIGIWAY Spring Return auto-calibration troubleshooting

      General advice for setting up Fit the unit and arm as per the diagrams in the installation manual. The door must be completely free swinging with a physically defined close point - i.e. not a swing-through door. Any hydraulic or spring closing/hold ...
    • How do I calibrate the door operator?

      The DIGIWAY system benefits from an easy-to-use auto-calibration feature.  To successfully complete the auto-calibration, you will need to: Set the spring pre-load tension (learn more) Set the door limits (learn more) Initiate the auto-calibration ...
    • How do I set the door limits?

      To correctly auto-calibrate the DIGIWAY, first you need to set the spring pre-load tension.  For instructions for the full calibration process, see this article.  Once the spring pre-load tension is set, you can set the door limits by following these ...
    • How do I set the spring pre-load tension?

      First, open your DIGIWAY app and find the correct unit that you want to programme. Then, follow these steps to set the spring pre-tension: Hold down OK to enter the programming menu. From the menu, select Door Calibration and then Spring Preload. In ...